Please note the following criteria when choosing a location for the inverter:

  • Install only on a solid, non-flammable surface
  • Max. ambient temperatures: -25 °C / +60 °C
  • Relative humidity: 0-100%
  • The airflow within the inverter is from the left to the top (cold air taken in from the left, hot air dissipated out of the top).
  • The exhaust air can reach a temperature of 70 °C.
  • If the inverter is installed in a switch cabinet or a similar sealed area, then forced-air ventilation must be provided to ensure adequate heat dissipation.
  • If the inverter is to be installed on the outer wall of a cattle shed, maintain a minimum all-round clearance of 2 m between the inverter and all ventilation and other openings in the building.
  • The installation location must not be exposed to ammonia, corrosive vapours, salts or acids.